UPS Norden 100kVA / 100kW Double Conversion Tower Type 3/3 with 5inch LCD display (External Battery) CN933100U-5L
- Power Capacity: 100,000 VA / 100,000 W
- Output Waveform: Pure sine wave
- Internal Battery: 30–50 x 12V/9Ah (±180V ~ ±300VDC)
- External Battery Support: No
- Display: LCD showing load, battery, voltage, frequency, operation mode, bypass, and fault status
- Protections: EMI filter, surge protection, overload, overtemperature, short circuit, low battery, fan failure, EPO
- Connectivity: USB, RS232, RS485, parallel port, dry contact (optional SNMP, relay card)
- Weight: 147 kg
- Estimated Delivery : Up to 4 business days
- Free Shipping & Returns : On all orders over $200
UPS Norden 100kVA / 100kW Double Conversion Tower Type 3/3 UPS with 5inch LCD display is an online double-conversion UPS with three-phase input and output, featuring an output power factor of 1. Its tower-type design allows for parallel operation of up to 6 units, making it ideal for industrial and critical business applications that require strict voltage regulation.
General Features
-
Wide Input Voltage Range: Compatible with unstable power environments thanks to its wide 140–485Vac range (phase: 80–280Vac).
-
High Input Power Factor (up to 0.99): Reduces electrical losses and improves energy efficiency.
-
Superior High Efficiency: With a three-level inverter, the UPS achieves up to 96% efficiency, optimizing operational performance.
-
Output Power Factor 1.0: Delivers 100% real power, ensuring efficient operation with all load types, including unbalanced loads.
-
Supports up to 6 Units in Parallel: Enables capacity expansion or N+X redundancy setup, increasing flexibility and system reliability.
-
Low Input Current Harmonic (<3% THDi): Reduces grid pollution and protects the shared power system.
-
High Charging Current, Flexible Battery Configuration: Supports 30–50 battery cells, adaptable to various backup requirements.
-
High Load Compatibility: Operates reliably with inductive, capacitive, and unbalanced loads.
-
Power Walk-in Function: Limits inrush current during startup, protecting generators and extending equipment lifespan.
-
LBS (Load Bus Synchronization): Allows two independent UPS systems to synchronize, enhancing power continuity and safety.
-
Versatile Communication: Supports USB, RS232, RS485, with optional expansions like SNMP and dry contact card for remote monitoring.
Power Capacity | |
VA | 100,000 |
Watts | 100,000 |
Input | |
Input Voltage | 380/400/415Vac (3Ph+N+PE) |
Input Voltage Range | 138~305Vac for 40% Load; 305~485Vac for Full Load |
Operating Frequency Range | 40~70Hz |
Input Power Factor | ≥0.99 |
Maximum Voltage | 220Vac:+25% (options: +10%, +15%, +20%) |
230V: +20% (options: +10%, +15%) | |
240V: +15% (option: +10%) | |
Minimum Voltage | -45% (options: -20%, -30%) |
Bypass Frequency Range | ±10% |
Generator Compatibility | Supported |
Input THDi | <3% (linear load) |
Output | |
Output Voltage | 380/400/415Vac (3Ph+N+PE) |
Output Power Factor | 0.9 |
Voltage Regulation | ±1% |
Frequency Range (Line Mode) | ±1% / ±2% / ±4% / ±5% / ±10% of nominal frequency (Selectable) |
Frequency Range (Battery Mode) | 50/60Hz (±0.2%) |
Crest Factor | 3:01 |
Output THDv | ≤2% (linear load), ≤4% (non-linear load) |
Battery | |
Battery Voltage | ±180 to ±300Vdc (30–50 batteries of 12V each) |
Charging Current | 40A |
System Features | |
Transfer Time | 0ms (mains to battery / mains to bypass) |
Overload (Line Mode) | ≤110%: 60 minutes |
≤150%: 1 minute | |
>150%: bypass in 1.2 seconds | |
Overload (Bypass Mode) | 30°C: 135% long-term |
40°C: 125% long-term | |
>1000%: 100ms | |
Alarms | Overload, utility fault, UPS fault, low battery, etc. |
Protections | Short circuit, overload, overtemperature, low battery, fan failure |
Communication Interfaces | USB, RS232, RS485, Parallel port, Dry contact, Smart slot, LBS, SNMP card (optional), Relay card (optional) |
Environmental | |
Operating Temperature | 0~40°C |
Storage Temperature | -25~55°C |
Humidity Range | 0~95% RH (Non-condensing) |
Altitude | <1500m |
Noise Level | <62dB |
Standards | |
Safety | IEC/EN62040-1, IEC/EN62477-1 |
EMC | IEC/EN62040-2 (IEC61000-2-2, 4-2 ~ 4-11) |
Physical | |
Dimensions (WxDxH) | 442 × 850 × 1200 mm |
Net Weight(kg) | 147 |