UPS Norden 150kVA / 150kW Double Conversion Tower Type 3/3 with 5inch LCD display (External Battery) CN933150U-5L
-
Power Capacity: 150,000 VA / 150,000 W
-
Waveform: Pure sine wave
-
Battery: 30–50 x 12V (±180V ~ ±300VDC)
-
Charging Current: 60A
-
Display: LCD – voltage, load, frequency, mode, fault, battery
-
Protection: Overload, short circuit, overtemperature, fan/UPS/power failure, low battery
-
Alarm: Audible + LCD display
-
Communication Interfaces: USB, RS232, RS485, dry contact, SNMP slot / relay card
-
Transfer Time: 0ms (to battery / bypass)
-
Noise Level: <60 dB
-
Dimensions: 442 × 850 × 1200 mm
-
Weight: 190 kg
- Estimated Delivery : Up to 4 business days
- Free Shipping & Returns : On all orders over $200
UPS Norden 150kVA / 150kW Double Conversion Tower is an online double conversion UPS system with three-phase input and output, featuring a power factor of 1. Its tower-type design supports parallel operation of up to six units, making it ideal for industrial and critical business applications with strict voltage regulations.
General Features
-
Wide Input Voltage Range: Compatible with unstable power environments thanks to a wide range of 140–485Vac (phase: 80–280Vac).
-
High Input Power Factor (up to 0.99): Reduces power loss and improves energy efficiency.
-
Superior High Efficiency: With a three-level inverter, the system achieves up to 96% efficiency, optimizing operational performance.
-
Output Power Factor 1.0: Delivers 100% real power, effectively supporting all types of loads, including unbalanced loads.
-
Supports up to 6 Units in Parallel: Enables capacity expansion or N+X redundancy configuration, enhancing flexibility and reliability.
-
Low Input Current Harmonic Distortion (<3% THDi): Minimizes interference to the power grid, protecting the common power system.
-
High Charging Current and Flexible Battery Configuration: Supports battery groups of 30–50 cells, meeting various backup power requirements.
-
High Load Compatibility: Operates stably with inductive, capacitive, and unbalanced loads.
-
Power Walk-in Function: Limits inrush current during startup, protecting generators and extending equipment lifespan.
-
LBS (Load Bus Synchronization) Function: Allows two independent UPS systems to synchronize, enhancing power continuity and safety.
-
Versatile Communication: Supports USB, RS232, RS485, with optional expansions like SNMP and dry contact cards for remote monitoring.
| Power Capacity | |
| VA | 150 000 |
| Watts | 150 000 |
| Input | |
| Input Voltage | 380/400/415Vac (3Ph+N+PE) |
| Input Voltage Range | 305~485Vac (full load) 138~305Vac (load 40%) |
| Operating Frequency Range | 40~70Hz |
| Input Power Factor | ≥0.99 |
| Maximum Voltage | 220Vac:+25% (options: +10%,+15%,+20%) 230V: +20% (options: +10%,+15%) 240V: +15% (option: +10%) |
| Minimum Voltage | -45% (options: -20%,-30%) |
| Bypass Frequency Range | ±10% |
| Generator Compatibility | Supported |
| Input THDi | <3% (linear load) |
| Output | |
| Output Voltage | 380/400/415Vac (3Ph+N+PE) |
| Output Power Factor | 0.9 |
| Voltage Regulation | ±1% |
| Frequency Range (Line Mode) | ±1%/±2%/±4%/±5%/±10% of nominal frequency (Selectable) |
| Frequency Range (Battery Mode) | 50/60(±0,2%)Hz |
| Crest Factor | 3:1 |
| Output THDv | ≤2% (linear load), ≤4% (non-linear load) |
| Battery | |
| Battery Voltage | ±180/±192/±204/±216/±228/±240/±252/±264/±276/±288/±300Vdc (30/32/34/36/38/40/42/44/46/48/50 pcs) |
| Charging Current | 60A |
| System Features | |
| Tranfer time | 0ms (mains to battery / mains to bypass) |
| Overload (Line Mode) | ≤110%: 60 minutes ≤150%: 1 minute >150%: transfer to bypass in 1.2 seconds |
| Overload (Bypass Mode) | 30°C: 135% long-term 40°C: 125% long-term >1000%: 100ms |
| Alarms | Overload, utility fault, UPS fault, low battery, etc. |
| Protections | Short circuit, overload, overtemperature, low battery, fan failure |
| Communication Interfaces | USB, RS232, RS485, Parallel port, Dry contact, Smart slot, LBS, SNMP card (optional), Relay card (optional) |
| Environmental | |
| Operating temperature | 0~40°C |
| Storage temperature | -25~55°C |
| Humidity range | 0~95% (Non-condensing) |
| Altitude | <1500m |
| Noise level | <60db |
| Standards | |
| Safety | IEC/EN62040-1, IEC/EN62477-1 |
| EMC | IEC/EN 62040-2 (IEC 61000-2-2, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC61000-4-11) |
| Physical | |
| Dimension WxDxH(mm) | 442x850x1200 |
| Net Weight (kg) | 190 |