UPS Norden 15kVA / 13.5kW Double Conversion Tower Type 3/3 with 5inch LCD display (External Battery) CN93315U-5L
Power capacity: 15,000 VA / 13,500 W
Output waveform: Pure sine wave
Internal battery: 16/18/20 x 12V/9Ah (±96/108/120Vdc)
External battery support: None
Display: LCD showing load, battery, voltage, frequency, operation mode, bypass, and fault status
Protection: EMI filter, surge protection, overload, overtemperature, short circuit, low battery, fan failure, EPO
Communication: USB, RS232, RS485, parallel port, dry contact (optional SNMP, relay)
Weight: 39 kg
- Estimated Delivery : Up to 4 business days
- Free Shipping & Returns : On all orders over $200
UPS Norden 15kVA / 13.5kW Double Conversion Tower Type 3/3 with 5-inch LCD display is a true online double conversion UPS with three-phase input and output, and an output power factor of 0.9. This tower-type UPS features high power density, supports parallel redundancy, and offers ECO operating mode for energy savings.
Key Features
True online double conversion technology with DSP (Digital Signal Processor) for high performance and stability.
Supports N+X parallel redundancy, up to 4 units operating simultaneously.
Low input current harmonic distortion, THDi < 3%, minimizing impact on the power system.
Wide input voltage range: 208–478Vac.
Flexible input frequency: 40–70Hz, compatible with various power sources.
Optimized battery system, supports 16/18/20 batteries, maximum charging current up to 18A (optional).
Generator compatible, ensuring continuous power in industrial environments.
Smart ECO mode helps maximize energy savings when conditions permit.
Intelligent fan speed adjustment based on load, improving efficiency and reducing noise.
Self-diagnosis at startup, ensuring stable system operation from the beginning.
Flexible frequency conversion 50Hz/60Hz, compatible with a wide range of equipment.
Model | CN7315MP | |
Capacity | VA | 15000 |
Watts | 13500 | |
Input | Normal Voltage | 380/400/415Vac; (3Ph+N+PE), 220/230/240Vac (L+N+PE) |
Operating Voltage Range | 208~478Vac; 120~276Vac | |
Operating Frequency Range | 40~70Hz (50/60Hz Auto-Sensing) | |
Power Factor | ≥0.99 | |
Bypass voltage range | Max.voltage: 220V: +25%(optional +10%,+15%,+20% ) | |
230V: +20% (optional +10%,+15%), | ||
240V: +15% (optional +10%) | ||
Min.voltage: -45% (optional -20%,-30%) | ||
Bypass Freq Range | Frequency protection range:±10%Frequency protection range:±10% | |
Generator Input | Support | |
Output | Rated voltage | 220/230/240Vac |
Power Factor | 0.9 | |
Voltage Regulation | ±1% | |
Freq. Line mode | ±1%/±2%/±4%/±5%/±10% of the rated frequency(optional) | |
Freq. Bat. mode | 50Hz / 60Hz (±0.1)Hz | |
Crest Factor | 3:01 | |
Harmonic Distortion (THDv) | ≤2% with linear load, ≤5% with non-linear load | |
Efficiency | >93.5% | |
Battery | Battery Voltage | 192/216/240Vdc(16/18/20pcs) |
Typical recharging Time | 6~8 hours (to 90% of full capacity) | |
Charging current | 16A( Max.) | |
System features | Transfer time | Mains to battery:0ms; Inverter to bypass:0ms |
Overload | Line mode: Load≤110%: last 60min, ≤125%: last 10min, ≤150%: last 1min, >150% turn to bypass mode immediately | |
Bypass mode: 63A(Breaker) | ||
Short circuit | Hold whole system | |
Overheat | Line mode: Turn to bypass; Backup mode: shut down UPS immediately | |
Battery low | Alarm and switch off | |
Self-diagnostics | Upon power on and software control | |
Battery | Advanced battery management | |
Audible & Visual alarms | Line failure, Battery under voltage, Overload, System fault | |
LED and LCD Display | Line mode, Bat. mode, Eco mode, Bypass mode, Battery under voltage, Overload & UPS Fault | |
LCD Display | Input voltage, Input frequency, Output voltage, Output frequency, Load percentage, Battery voltage, Inner temperature & Remaining battery backup time | |
Communication interface | RS232, USB,SNMP card(optional), Parallel card(optional), Relay card (optional) | |
Environment | Operating temperature | 0~40°C |
Storage temperature | -25~55°C | |
Humidity range | 0~95% (Non-condensing) | |
Altitude | <1500m | |
Noise Level | <55dB at 1 Meter | |
Physical | Dimension | 220 x 531 x 450 |
Weight | 24 | |
Standards | Safety | IEC/EN62040-1, IEC/EN62477-1 |
EMC | IEC/EN62040-2, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8, IEC61000-4-11, IEC61000-2-2 |